EICHER POWERES GENSET TECHNICAL SPECIFICATION |
| Genset Model |
|
VE-160 |
| Genset Rating |
KVA / kWe |
160 / 128 |
| Power Factor |
lagging |
0.8 |
| Engine Rated Power |
HP |
201 |
| Cooling System |
|
Liquid Cooled |
| Current Amp |
Amps |
223 A |
| ENGINE TECHNICAL DETAILS |
| Engine Make |
|
EICHER |
| Engine Model |
|
EE694TCI |
| No. of Cylinders |
No. |
6 – inLine |
| Nature of Aspiration |
|
Turbocharged Intercooled |
| Displacement |
Liters |
5.7 |
| Compression Ratio |
|
17.5:01 |
| Fuel |
|
High Speed Diesel |
| Bore |
MM |
100 |
| Stroke |
MM |
120 |
| Electric System |
Volt |
12 V DC |
| Total Coolant Capacity |
Liters |
21.5 |
| Lube Oil Consumption |
% F. Cons |
0.1 |
| Lube Oil System Capacity |
Liters |
23.8 |
| Lub. Oil change Period |
Hours |
500 |
| Lube Oil Standard |
|
15W40CI Standard |
| Type of Governor |
Type |
Electronic |
| Class of Governing |
|
Calss – A1 |
| Battery Capacity |
AH |
135AH |
| ALTENATOR TECHNICAL DETAILS |
| Alternator Make |
|
STAMFORD |
| Alternator Type |
|
SELF REGULATED/SELF EXCITED/BRUSHLESS |
| Type of Insulation |
|
IP 23, Class H |
| No. of Phase / Voltage |
Volt |
415 Volt Three Phase |
| Maximum Unbalanced Load Phasewise |
% |
less than or equal to 25% |
| Voltage regulation |
% |
±1 Percentage |
| Frequency |
Hz |
50 Hz |
| CONTROL PANEL TECHNICAL DETAILS |
| Control Panel Model |
|
MANUAL (Standard) Panel With DSC Controller DSC4520 |
| Type of Panel |
|
MANUAL (Standard) / Auto Mains Failure (Optional) |
| Make of Controller |
|
Deep-sea/Equivalent Reputed make |
| Location |
|
Mounted Inside Acoustic Enclosure |
| Type of MCB/MCCB |
3P/4P |
3P MCCB |
| Current Breaking Capacity |
Amps |
250 |
| Metering of Alternator |
|
Frequency, Line to Line Voltage and Line to Neutral Voltage, Current AMP, kVA |
| Metering of Engine |
|
Engine Running Hours, Engine Temperature, Oil Pressure, Starting Battery Voltage |
| Protection |
|
High/Low Coolant Temperature, Low Lube Oil Pressure, Battery Over Voltage / Under Voltage / Weak Volts, Fail to Start, Sensor Failure, Cranking Lockout, Low Fuel Level, Over Voltage / Under Voltage, Frequency |
| ACOUSTIC ENCLOSURE TECHNICAL DETAILS |
| Type of Canopy |
|
Outdoor Type, Ready to use – (CPCB-II Complaint) |
| Noise Level |
dB |
75 dB at 1 Meter |
| Fuel Tank Capacity |
Liters |
320 Liters |
| Fuel Tank Location |
|
Mounted at base Inside Acoustic Enclosure |
| Engine & Alternator Mounting |
|
Engine and alternator are mounted on a common MS fabricated base frame with AVM pads. Inside Acoustic Enclosure |
| Acoustic Enclosure Size in “mm” |
L |
3800 |
| W |
1400 |
| H |
1820 |
| Genset With Acoustic Enclosure Weight |
Kgs |
2400 |
# Power rating as per standard reference condition as per –BS 5514 / ISO 3046 / ISO 8528/ IS 10002. # Fuel consumption data is based on diesel having specific gravity of 0.85. Fuel consumption tolerance is +5% # All technical specifications are subject to change due to continuous product development without prior notice. # Diesel Generators are manufactured by authorized OEA of VE Commercial Vehicles Ltd. in different design and color. |