Diesel Generator Set 50 kVA

Overview of PRODUCT​

50 KVA, Three Phase, 415 Volt, 50 Hz, 0.8 P.F.
POWER Engineering India Pvt Ltd Make Silent Water Cooled Diesel Generator Set Model No VE-50 comprising of Eicher engine model Eicher-E483TCI. 4 No of Cylinders Engines developing 65 HP, STAMFORD alternator rated at 50 KVA, 415 Volt.

Fuel Consumption at 90% Load = 6.5 Liters Per Hours

EICHER POWERES GENSET TECHNICAL SPECIFICATION

Genset Model VE-50
Genset RatingKVA / kWe50 / 40
Power Factorlagging0.8
Engine Rated PowerHP65
Cooling System Liquid Cooled
Current AmpAmps70 A
ENGINE TECHNICAL DETAILS 
Engine Make EICHER
Engine Model EE483TCI
No. of CylindersNo.4 – inLine
Nature of Aspiration Turbocharged Intercooled
DisplacementLiters3.3
Compression Ratio 17:01
Fuel High Speed Diesel
BoreMM100
StrokeMM105
Electric SystemVolt12 V DC
Total Coolant CapacityLiters15
Lube Oil Consumption% F. Cons0.1
Lube Oil System CapacityLiters11
Lub. Oil change PeriodHours500
Lube Oil Standard 15W40CI Standard
Type of GovernorTypeMechanical
Class of Governing Calss – A1
Battery CapacityAH100AH
ALTENATOR TECHNICAL DETAILS 
Alternator Make STAMFORD
Alternator Type SELF REGULATED/SELF EXCITED/BRUSHLESS
Type of Insulation IP 23, Class H
No. of Phase / VoltageVolt230 V Single phase or 415 V Three Phase
Maximum Unbalanced Load Phasewise%less than or equal to 25%
Voltage regulation%±1 Percentage
FrequencyHz50 Hz
CONTROL PANEL TECHNICAL DETAILS 
Control Panel Model MANUAL (Standard) Panel  With DSC Controller DSC4520
Type of Panel MANUAL (Standard) / Auto Mains Failure (Optional)
Make of Controller Deep-sea/Equivalent Reputed make
Location Mounted Inside Acoustic Enclosure
Type of MCB/MCCB3P/4P3P MCCB
Current Breaking CapacityAmps100
Metering of Alternator Frequency, Line to Line Voltage and Line to Neutral Voltage, Current AMP, kVA 
Metering of ƒEngine  Engine Running Hours, Engine Temperature, Oil Pressure, Starting Battery Voltage 
Protection High/Low Coolant Temperature, Low Lube Oil Pressure, Battery Over Voltage / Under Voltage / Weak Volts, Fail to Start, Sensor Failure, Cranking Lockout, Low Fuel Level, Over Voltage / Under Voltage, Frequency
ACOUSTIC ENCLOSURE TECHNICAL DETAILS 
Type of Canopy Outdoor Type, Ready to use – (CPCB-II Complaint)
Noise LeveldB75 dB at 1 Meter
Fuel Tank CapacityLiters130 Liters
Fuel Tank Location Mounted at base Inside Acoustic Enclosure
Engine & Alternator Mounting ƒEngine and alternator are mounted on a common MS fabricated base frame with AVM pads.
Inside Acoustic Enclosure
Acoustic Enclosure Size in “mm”L2685
W1080
H1455
Genset With Acoustic Enclosure WeightKgs1400
# Power rating as per standard reference condition as per –BS 5514 / ISO 3046 / ISO 8528/ IS 10002.
# Fuel consumption data is based on diesel having specific gravity of 0.85. Fuel consumption tolerance is +5%
# All technical specifications are subject to change due to continuous product development without prior notice.
# Diesel Generators are manufactured by authorized OEA of VE Commercial Vehicles Ltd. in different design and color.